All-in-one Liquid-cooled ESS Cabinet

ECO-E261LP-2A

The ECO-E261LP-2A features advanced pack-level liquid cooling
and temperature balancing, maintaining cell temperature differences within 3 ℃. This enhances cell temperature consistency and extends battery life. Its modular design enables flexible parallel configurations and higher energy density, significantly improving the cost-effectiveness, safety, and installation convenience of ESS projects.

261 kWh / 1P260S

System Configuration

125

kW

Rated Output Power

400

V

Rated AC Voltage

89

%

Max. Round Trip Eficiency.

≥ 8,000

Cycle Life

IP55

Ingress Rating

ECO-E261LP-2A

Product Features

Compact

1.4m² footprint only, easy transportation & fast
installation.

High Integration

261kWh energy in one cabinet with remarkable
endurance.

Efficient Cooling

Optimal in-PACK duct design, achieve
high - efficient cooling and low energy consumption.

Long Cycle Life

Over 8,000 times cycle life, excellent performance
of battery system.

Flexible Expansion

Modular design, simplified parallel
expansion.

Ultimate Safety

In-PACK fire warning and protection
with aerosol, prevent heat diffusion and runaway.

Specification

DC Side
Cell Type LFP / 314 Ah
Pack Configuration 52.2 kWh / 1P52S
System Configuration 261 kWh / 1P260S
Rated DC Voltage 832 V
DC Voltage Range
728 ~ 936 V
Max. Charge/Discharge Rate 0.5 P
Max. Depth of Discharge 100% (25 ± 2 ℃)
AC Side
Rated Output Power 125 kW
Rated AC Voltage 400V
AC Voltage Range ±15%
Grid Type 3W+N+PE
Rated Frequency 50 Hz / 60 Hz
Power Factor 0.99/ -1 ~ +1
THDi ≤ 3%
DC Ratio <0.5% Ipn
General
Max. Round Trip Efficiency 89%
Cycle Life ≥ 8,000 cycles
Communication Modbus TCP/IP
Fire Suppression System Aerosol
Ingress Rating IP55
Cooling Liquid cooling+Forced air cooling
Operating Temperature -25℃~55℃ (Derating after 45℃)
Anticorrosion Rating C4 (C5 optional)
Humidity 0~95% RH (non-condensing)
Noise ≤ 75 dB
Altitude 3000m (Derating above 2000m)
Dimensions (W*D*H) 1,050*1,350*2,400 mm
Weight 2,600 kg
Safety/EMC UN38.3, IEC62619, IEC63056, IEC62477-1, IEC61000-6-2/4, UL9540A
Grid code EN50549-1/-10, EN50549-2/-10, G99, VDE4105,
NRS097, C10/11, CEI0-21, CEI0-16