STS Cabinet
ECO-STS-C125-2/4/6IN
Elecnova ECO-STS-C125-2/4/6IN is a seamless on/off-grid switching cabinet designed for the 125kW rated power Elecnova all-in-one ESS cabinet within 20ms switching time. It enables on/off-grid switching for single or multiple parallel-connected application.Equipped with reserved ports for PV inverter power and critical loads connection, allowing for the normal operation of PV system and loads in grid outage condition.
6 * 250A
Max. ESS Current
6 * 125kW
Rated ESS Power
1600A
Max. Grid Current
800A
Max. PV&Loads Port Current
550 kW
Recommended Max. PV Power
550 kW
Recommended Max. Load Power*
Intelligent collaboration
Seamless on/off-grid switching within 20ms.
Reliable
Leading brands selection of all equipments, safe
and reliable.
Highly Integration
Integrate STS, UPS, meter, breakers, ATS(optional) and other
accessories in one system, compact and easy transportation.
Electrical Safety
Backup design and assurance of critical loads
without interuption.
| ESS Side Parameters |
ECO-STS-C125-2IN
ECO-STS-C125-4IN
ECO-STS-C125-6IN
|
| Max. No. of ESS Connection |
2 units
4 units
6 units
|
| Max. ESS Current |
2*250A
4*250A
6*250A
|
| Rated ESS Power |
2*125kW
4*125kW
6*125kW
|
| Grid Side Parameters | |
| No. of Grid Connection Port | 1 |
| Max. Grid Current |
500A
800A
1600A
|
| Grid Voltage Range | 400V±15% |
| Grid Type | 3W+N+PE |
| Rated Frequency |
50/60Hz |
| On/off-grid Switching Time | 20ms |
| PV Input Requirements | |
| Max. PV&Loads Port Current |
250A
630A
800A
|
| Recommended Max. PV Power |
170kW
430kW
550kW
|
| Recommended Max. Load Power* | 70% × ESS Power |
| Auxiliary Equipments Parameters | |
| UPS | Standard |
| Maintenance Socket | Standard, 16A |
| Surge Protection | AC Type Ⅱ |
| Meter Accuracy | 0.5S |
| ATS | Optional |
| General Parameters | |
| Dimension(W×D×H) |
800×1200×1800 mm
1000×1200×1800 mm
1200×1200×2200 mm
|
| Altitude | 3000m |
| Ambient Temperature | -15℃~45℃ |
| Humidity | 0~95%RH (non-condensing) |
| Cooling Method | Air cooling |
| IP Rating | IP54 |
| Communication | RS485, Modbus TCP/IP |